Last updated: November 2, 2026 at 1:20 PM UTC
All 957 Vulnerability 399 Breach 144 Threat 407 Defense 7
Tag: ics-ot (2 articles)Clear

Attackers hijack Danfoss refrigeration controllers to spoil stock across hundreds of French supermarket stores

Attackers hijacked refrigeration controllers running older Danfoss control software at several French supermarket chains, including Intermarche, Carrefour Market, Monoprix, and Leclerc, abusing a built-in defrost feature to raise temperatures and spoil stock. French outlets reported 250 to 350 affected stores, significant financial losses, and food waste, and the Paris prosecutor opened an investigation. Researchers linked two flaws in the Danfoss AK-SM 8xxA platform, CVE-2025-41450 for authentication bypass and CVE-2025-41451 for command injection, though how the controllers were reached is unconfirmed. One researcher found 2,752 Danfoss systems exposed online, 1,590 of them in France.

Check
Inventory internet-exposed Danfoss AK-SM 8xxA refrigeration controllers, remove them from direct internet access, update to current firmware, and review for unauthorized configuration changes.
Affected
Internet-exposed Danfoss refrigeration controllers on older software can be hijacked to manipulate defrost and temperature settings, spoiling stored goods, as seen across hundreds of French stores.
Fix
Place refrigeration controllers behind VPN or network segmentation, patch Danfoss AK-SM platforms, enforce strong authentication, and monitor for unexpected setpoint or defrost changes.

US agencies say Iran-linked actors are disrupting water and energy control systems

CISA, the FBI, NSA, EPA, and Department of Energy updated a joint advisory warning that Iran-affiliated actors are exploiting internet-facing operational technology across US critical infrastructure, and in some cases disrupting it. Since at least March 2026 the group has targeted programmable logic controllers, the small industrial computers that run automation processes, extracting device project files and then modifying or deleting the control logic. Water, wastewater, energy, and government facilities are among the affected sectors, and some victims experienced operational disruption and financial loss. The July update broadened the range of affected device makers, added detection guidance, and refreshed the published indicators of compromise.

Check
Take internet-facing PLCs and operational technology offline or behind a VPN, change default and weak device passwords, and check for unexpected changes to control logic and project files.
Affected
Water, wastewater, energy, and government operators with internet-exposed programmable logic controllers; attackers extract project files and alter control logic, which can push processes into unsafe states.
Fix
Remove operational technology from direct internet exposure, enforce strong unique credentials and multi-factor authentication, segment control networks, back up device logic offline, and apply the advisory's detection guidance and indicators.